IBase Workspace
To work with IBase, you need to use the following workspaces.
When you install IBase, a System Information node is added to System Browser under: Application > Advanced Application > System Information.
When you select System Information, the Extended Operation tab displays a list of properties that you can set to configure the behavior of the IBase report.

System Information Properties | |
Property Name | Description |
Summary Status1) 2) | Displays the summary status. |
Active1) | Default value is |
Policy Compliance1) | Default value is |
Last Collection Started At1) | Displays the date and time when the last IBase information collection started. |
Last Collection Finished1) | Displays the date and time when the last information collection was finished and the IBase report was generated. |
Equip.ID-Default1) 2) | This is the default equipment ID that is used when no Equipment ID is provided for a discipline. |
Equip. ID-Management System1) 2) | Provide the equipment ID for the discipline Management System; otherwise the default will be used during IBase report generation. |
Equip. ID-Building Infrastructure1) 2) | Provide the equipment ID for the discipline Building Infrastructure, otherwise the default will be used during IBase report generation. |
Equip. ID-Building Automation1) 2) | Provide the equipment ID for the discipline Building Automation; otherwise the default will be used during IBase report generation. |
Equip. ID-Fire1) 2) | Provide the equipment ID for the discipline Fire; otherwise the default will be used during IBase report generation. |
Equip. ID-Security1) 2) | Provide the equipment ID for the discipline Security; otherwise the default will be used during IBase report generation. |
Equip. ID-Energy Management1) 2) | Provide equipment ID for the discipline Energy Management; otherwise the default will be used during IBase report generation. |
Equip. ID-Notification1) 2) | Provide the equipment ID for the discipline Notification; otherwise the default will be used during IBase report generation. |
ID given by Customer1) | Provide the ID for the system provided by the customer. |
ID given by Operator1) | Provide the ID given by the operator working with the system. |
ID given by Vendor1) | Provide the ID given by vendor. |
Output Filename1) | Location and name of the IBase report generated. |
Signature recalculation Interval | Provide the time interval when the checksum report is to be generated with new data |
Site ID | Provide the site ID of the customer site. |
1) | For each property, click Apply to set the entered value for each property. |
2) | Configurable only in the Extended Operation tab. |
When you install IBase, a pre-configured reaction known as timing becomes available in the Reaction Editor tab when you select Applications > Macros > Logics > Reactions > System Information > Timing.
This is used during the automatic execution of the IBase script. Thus the IBase script will execute automatically if all the conditions configured in it are valid.
You can modify the reaction (Timing). For example, you can change the time and/or day when the IBase script execution starts.

The IBase script is selected under Applications > Logics > Scripts > System Information and its Status is Idle
in the Extended Operation tab.
When working in Engineering mode, the Script Editor displays the IBase script that can be executed manually or automatically.
During IBase script execution, the IBase script traces information messages which can be viewed in the Console expander of the Script Editor. Similarly, the error messages, can be viewed in the Error List expander.
On successful execution, the IBase script generates the IBase report for the system.